PDF Печать E-mail


DOI: https://doi.org/10.15407/techned2016.03.091

CORRECTION OF ERRORS IN THE REMOTE MEASUREMENT OF THE PHASE DIFFERENCE BETWEEN THE ELECTRIC SIGNALS

Journal Tekhnichna elektrodynamika
Publisher Institute of Electrodynamics National Academy of Science of Ukraine
ISSN 1607-7970 (print), 2218-1903 (online)
Issue № 3, 2016 (May/June)
Pages 91 – 96

 

Author
Borshchev P.I.
Institute of Electrodynamics National Academy of Science of Ukraine,
Pr. Peremogy, 56, Kyiv-57, 03680, Ukraine,
e-mail: Этот e-mail адрес защищен от спам-ботов, для его просмотра у Вас должен быть включен Javascript

 

Abstract

The errors of the measurement of the phase difference between the alternating currents flowing through the remote objects of control are analyzed. A substantial impact on the result of the measurement values of the clock frequency of remote measurement modules is noted. It is shown that the additive component of error is unacceptably high, which doesn’t satisfy the requirements of the problem diagnostic of the condition of high-voltage capacitor isolation under operating voltage. A method of reducing the error based on the multiplicative correction of measurements of time intervals from the start of sampling until the transition the input signals through zero is proposed. Usage of this method can reduce the error to a level that ensures the necessary metrological characteristics of the measuring system. References 8, figure 1.

 

Key words: phase difference, remote measurement, high voltage insulation, loss tangent, measurement under operating voltage, multiplicative correction of errors.

 

Received:    05.01.2016
Accepted:     05.02.2016
Published:   25.04.2016

 

References

1. Borshchov P.I. Remote measurement of electric parameters of high voltage insulation under operating voltage. Tekhnichna Elektrodynamika.  2015.  No 5.  P. 90-93. (Rus)
2. Borshchov P.I. Selective device for measuring electrical quantities at power frequency. Tekhnichna Elektrodynamika.  2005.  No 4.  P. 74-78. (Rus)
3. Novitskii P.V., Zograf I.A. Estimates of the error of measurement results.  Leningrad: Enerhoatomizdat.  1991.  304 p. (Rus)
4. Stohnii B.S., Pylypenko Y.V., Sopel M.F., Tutik V.L. Hardware-software complex for continuous diagnostic of isolation of current transformers and high-voltage bushings of power transformers. Pratsi Instytutu elektrodynamiky Natsionalnoi Akademii Nauk Ukrainy.  2010.  No 26.  P. 38-45. (Rus)
5. Geyer quartz technology. Quartz crystal HC-49U. Available at: http://www.geyer-electronic.de/uploads/tx_userartikelfrequenz/GEYER-KX-49-V1_16.pdf (accessed 21.12.2015).
6. GPS/GLONASS/GALILEO/SBUS RECEIVERS NV08C-CSM v/3/x, v.4.x. Datasheet. Version 2.7. Available at: http://www.nvs-gnss.com/products/receivers/item/download/77.html (accessed 21.12.2015).
7. RM0008. STM32F101xx, STM32F102xx, STM32F103xx, STM32F105xx and STM32F107xx advanced ARM -based 32-bit MCUs. Reference manual. Available at: http://www.st.com/web/en/resource/technical /document/reference_manual/CD00171190.pdf (accessed 21.12.2015).
8. TMU 100. Monitoring system for high-voltage bushings and on-load tap changers. Available at: https://library.e.abb.com/public/742ebb4cde015790c1257b44003695c3/1ZDE000011%20en_flyer%20TMU%20100.pdf (accessed 21.12.2015).

 

PDF