Abstract
Device for measuring of difference of loss factors and capacitance ratio of the high-voltage insulations under operating voltage is described. Influence of voltage between points grounding insulations and device is suppressed by electrical isolation of power and control of the measuring channels. Excludes current transformers, whereby reduced error measurement of loss factor. References 4, figures 2.
References
Beliaev V.K., Borshchov P.I., Obodovskii V.D., Kanivetskii Yu.V., Bekhtev G.V., Bogdanov S.G., Masenko D.A., Dvoinykh V.P. Instrumentation and monitoring experience of insulation condenser type under operating voltage // Elektricheskie Seti i Sistemy. – 2012. – № 4. – Pр. 68–72. (Rus)
Sakhno A.А. Measuring algorithm of loss factor of basic insulation of current transformers and bushings 330-750 kV in continuous monitoring under operating voltage // Elektrotekhnika і Elеktromekhanika. – 2010. – № 2. – Pр. 54–56. (Rus)
SOU-N ЕЕ 20.302:2007. Standards testing of electrical equipment. – Kharkiv: GRIFRE, 2009. – 278 p. (Ukr)
DSTU ІЕС 60044-1:2008. Measuring transformers. Part 1. Current transformers. – Кyiv: Derzhspozhyv standart Ukrainy. – 2010. – 42 p. (Ukr)

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Copyright (c) 2023 Array