Abstract
Geometrical parameters and number of air inclusions in solid insulation are defined on the basis of the decision of equation Volterra only in case of monotonous change of differential peak spectra (DPS) of pulses of partial dischargers. Otherwise the average parameter of air inclusions are defined. The estimation of quality of solid insulation is carried out by representation of set DPS in double logarithmic scale. Comparison of curves DPS is carried out on width of a strip of spectra of partial dischargers without mathematical processing. References 13, tables 1, figures 5.
References
Kuchinskii G.S. Partial dischargers in high-voltage designs. - Leningrad: Energia, Lenmgradskoe otdelenie. 1979. - 224 p. (Rus.)
Naboka B.G., Besprozvannych A.V., Gladchenko V.Ya. Diagnostics of high-voltage isolation with die help multichannel analyzer // Elektrichestvo. -1991. - № 5. - P. 5-9. (Rus.)
Naboka B.G., Besprozvatmych A.V., Gladchenko V. Ya. Slow processes in solid dielectric and optimum temperature of polymerization // Elektrichestvo. - 2003. - № 5. - P 51-54. (Rus.)
Naboka B.G., Besprozvannych А.V., Gladchenko V. Ya. Technique of measurement of differential peak spectra of pulses of partial dischargers // Elektrichestvo. -1990. - №11. - P. 71-74 (Rus.)
Rezinkina М.М., Shcherba A.A. Diagnostics and monitoring of high-voltage power electric cables with polyethylene insulation // Tekhnichna elektrodynamika. - 2008. - № 5. - P. 84-87. (Rus.)
Shidlovskii А.К., Shcherba A.A., Zolotarev V.V. and all. The analysis of micro heterogeneity of an electric field as factor of increase of intensity of electro physical processes in polymeric isolation of high-voltage cables and self- supporting isolated wires // Tekhnichna elektrodynamika. - 2008. - № 4. - P. 3-12. (Rus.)
Shidlovskii А.К., Shcherba A.A., Podoltsev A.D. and all. Modeling and the analysis of non-uniform electric fields in high-voltage power cables // Tekhnichna elektrodynamika. - 2006. - № 1. - P. 96-105. (Rus.)
Shuvalov М.Yu., Romashkin A.V., Ovsienko V.L. The analysis of defects m isolation of power high-voltage cables by methods of videomiroscopy and microexperiment // Elektrichestvo. - 2000. - № 5. - P. 49-57. (Rus.)
Catalogue of Hipotronics. - 2002. -10 p. (Rus.)
Cavallini A., Conti M., Montanari G. Early detection of electrical tree through advanced PD measurement inference techniques. - JICABLE: Versailles, France. - June 2003. - P. 612-616.
Rueth W. Calculation of insulation void density and size from partial discharge pulse height analysis. Annu. Report.: Conf. Elect. Insil. and Dielec. Phenom, Whitehaven. - 1981.
Shoji Hirabayschi, Ycshikasu Shibuya, Takatoshi Haseganwa. Estimation of the size partial discharge of voids in Coil Insulation of rotating machine // IEEE Trans. on Dielectrics and Electrical Insulation. - December 1974. - № 4.-P. 129-136.
Patent №1577524 SU A1 5G01 R31/14. Way of not destroying control of condensers with solid insulation / Naboka B.G.. Besprozvannych A.V., Gladchenko V.Ya., Malakhov V.A. (USSR). - Public 08.03.90. (Rus).
This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Copyright (c) 2023 Array