ANALYSIS OF TRANSIENT PROCESYS DURING ENERGISATION OF THE AC OVERHED TRANSMITION LINE IN THE HIBRID POWER SYSTEMS
ARTICLE_8_PDF (Українська)

Keywords

transient process
hybrid power system
switching overvoltage
aperiodic current
energisation,
transmission line перехідний процес
гібридна енергосистема
комутаційна перенапруга
аперіодичний струм
постановка під напругу
лінія електропересилання

How to Cite

[1]
Shpolianskii, O. 2022. ANALYSIS OF TRANSIENT PROCESYS DURING ENERGISATION OF THE AC OVERHED TRANSMITION LINE IN THE HIBRID POWER SYSTEMS . Tekhnichna Elektrodynamika. 6 (Oct. 2022), 058. DOI:https://doi.org/10.15407/techned2022.06.058.

Abstract

The paper analyses the transients that occur during the energisation of overhead transmission line 750 kV in a hybrid power system. It is shown that the power supply of the AC transmission line from the high voltage direct current transmission allows using converter control system to limit the switching overvoltage and the aperiodic currents. This enriches the list of traditional measures to improve the safety of AC power systems. References 8, tables 2, figures 1.

https://doi.org/10.15407/techned2022.06.058
ARTICLE_8_PDF (Українська)

References

CIGRE JWG C4/B4/C1 – 604: Influence of Embedded HVDC transmission on system security and AC network performance. CIGRE, Technical Brochure. 2013. P. 153.

Huang G.A., Krishnaswamy V. HVDC controls for power system stability. IEEE Power Engineering Society Summer Meeting. Chicago, IL, USA. July 21-25, 2002. Vol. 1. Pp. 597-602.

Arrillaga J., Elamin I.M. Transient Stability Performance of a 3-Machine System including an h.v. d.c. Link. Proceedings of the Institution of Electrical Engineers. 1976. Vol. 123. No 11. Pp. 1239-1244. DOI: https://doi.org/10.1049/piee.1976.0247

VSC-Based HVDC Transmission System (Detailed Model). URL: https://www.mathworks.com/help/physmod/sps/ug/vsc-based-hvdc-transmission-system-detailed-model.html;jsessionid=3b0fe7b63b98ce6b32dff8e63264 (accessed at 26.05.2022).

Khazaei J., Idowu P., Asrari A., Shafaye A.B., Piyasinghe L. Review of HVDC control in weak AC grids. Electric Power Systems Research. 2018. Vol. 162. Pp. 194-206. DOI: https://doi.org/10.1016/j.epsr.2018.05.022

Amin M., Molinas M., Lyu J., Cai X. Impact of power direction on the stability of VSC-HVDC seen from the impedance Nyquist plot. IEEE Transactions on Power Electronics. 2017. Vol. 32. No 10. Pp. 8204-8217. DOI: https://doi.org/10.1109/TPEL.2016.2608278

Barnes M., Beddard A. Voltage Source Converter HVDC Links – The state of the Art and Issues Going Forward. Energy Procedia. 2012. Vol. 24. Pp. 108-122. DOI: https://doi.org/10.1016/j.egypro.2012.06.092

Kuznetsov V.G., Tugai Yu.I., Shpolyansky O.G. Analysis of the preconditions of SF6 circuit breakers’ damage in 750 kV electric networks. Pratsi Instytutu elektrodynamiky Natsionalnoi Akademii nauk Ukrainy. 2017. Vyp. 47. Pp. 16-22. (Ukr) DOI: https://doi.org/10.15407/publishing2017.47.016

Creative Commons License