INVESTIGATION INTO THE EFFECTS OF CONDUCTOR TRANSPOSITION IN EXTRA HIGH VOLTAGE TRANSMISSION LINE’S ON ABNORMAL OVERVOLTAGE’S
ARTICLE_11_PDF (Українська)

Keywords

resonance overvoltage’s
longitudinal asymmetry of overhead line parameters
the open-phase operating conditions
model of transposed overhead line резонансні перенапруги
несиметрія параметрів лінії
неповнофазний режим
модель транспонованої лінії

How to Cite

[1]
Кузнецов, В., Тугай, Ю. and Кучанський, В. 2013. INVESTIGATION INTO THE EFFECTS OF CONDUCTOR TRANSPOSITION IN EXTRA HIGH VOLTAGE TRANSMISSION LINE’S ON ABNORMAL OVERVOLTAGE’S. Tekhnichna Elektrodynamika. 6 (Oct. 2013), 051.

Abstract

This article presents a novel approach to the study of practicable ratios of overvoltage’s in abnormal modes of transmission lines extra high voltage. An approach takes into account influence of asymmetry, which is caused by phase difference of overhead lines parameters. The method relies upon improved mathematical model of transposed transmission line, which permits comprehensive research of origin process anomalous overvoltage’s with real ratio of symmetrization. Researches of the following schemes of conductor transposition were made: line without transposition, not complete cycle of transposition, complete cycle of transposition and ideal transposed line. For the account real transposition in developed model was used equivalent matrix of line scheme which caused cascade connection of fourterminal networks. To research the conditions of abnormal overvoltage initiations were sated up equivalent circuits relative to switching – off phase of two accidents of open-phase modes: single-phase auto reclose and phase interruption. The functions of abnormal overvoltage’s were obtained on length and compensation ratio of overhead line, which were constructed for various transposition schemes. Critical values of line length for evolution abnormal overvoltage’s were determined. References 9, table 1, figures 3.

ARTICLE_11_PDF (Українська)

References

Beliakov N.N., Kadomskaia K.P., Levinshtein M.L. Processes at the single phase auto reclosing of high-voltage transmission line. − Мoskva: Energoatomizdat, 1991. – 256 p. (Rus)

Dmokhovskaia L.F. Engineering computation of internal overvoltage’s in transmissions lines. − Moskva: Energiia, 1972. − 288 p. (Rus)

Zilberman S.M., Krasilnikova Т.G., Manusov V.Z., Samorodov G.I. Transposition of overhead lines and its unexpected effect // Elektrichestvo. − 2006. − №5. − Pp. 11–16. (Rus)

Kostenko M.V., Perelman L.S. The simplest scheme of conductor transposition of three-phase overhead line // Elektrichestvo. − 1980. − №8. − Pp. 59–61. (Rus)

Kuznetsov V.G., Tugai Yu.I., Kuchanskyi V.V. Overvoltage’s at the open-phase conditions // Tekhnichna elektrodynamika. − 2012. − №2. − Pp. 40–41. (Ukr)

Levinshtein M.L., Khakimov F.Z. Compensation of second arc currents at single phase auto reclosing of electricity transmission lines with the single cycle of transposition // Izvestiya Akademii Nauk SSSR. Energetika i Transport. − 1988. − №5. – Pp. 45–51. (Rus)

Maikopar A.S. The arcing fault on the transmission lines. – Moskva: Energiia, 1968. − 200 p. (Rus)

J.A. Brandao Faria and M.V. Guerreiro das Neves. Resonance effects due to conductor transposition in threephase power lines // 14th PSCC, Sevilla, 24-28 June, 2002. − Pp. 10–15.

S. Tupsie, F. Isararamongkolrak and P.Pao-la-or. Analysis of Electromagnetic Field Effects Using FEM for Transmission Lines Transposition // World Academy of Science. Engineering and Technology. − 2009. − №3. − Pp. 33–39.

Creative Commons License

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.

Copyright (c) 2023 Array

Abstract views: 29 | PDF Downloads: 2

Downloads