THE RESEARCH OF MAGNETIC FIELD OF HIGH-VOLTAGE AC TRANSMISSIONS LINES
ARTICLE_1_PDF (Українська)

Keywords

transmission line
magnetic field
mathematical model
method of calculation
experimental researches линия электропередачи
магнитное поле
математическая модель
метод расчета
экспериментальные исследования

How to Cite

[1]
Розов, В., Реуцкий, С., Пелевин, Д. and Яковенко, В. 2012. THE RESEARCH OF MAGNETIC FIELD OF HIGH-VOLTAGE AC TRANSMISSIONS LINES. Tekhnichna Elektrodynamika. 1 (Jan. 2012), 003.

Abstract

The mathematical model of the 50 Hz three-phase overhead power transmission line and the engineering method of the calculation of the root mean square value of the magnetic field density are developed on the base of Bio–Savart’s and Laplace’s equations. The results of the experimental verification of the method developed are presented. They have been carried out on three operating transmission lines with the voltage 330 kV. The data show that the method developed provides the acceptable precision of the calculation with the relative error less than 10% at the distance of more than 10 m from the line. It is shown that with the nominal current 2 kA the induction of the magnetic field is equal to 3,7 mT on the border of the transmission line protection zone (38 m). It decreases to the safe level of 0,5 mT at the distance of more than 100 m from the line. This raises the problem of the formation of the size of sanitary protection zones taking into account not only electrical field but also the magnetic field. References 9, figures 3.

ARTICLE_1_PDF (Українська)

References

Neiman L.R., Demirchian K.S. Theory of Electrical Engineering: In 2 vol. – Leningrad: Energiia, 1967. – Vol.2. – 408 p. (Rus)

Stretton J. Electromagnetic Theory. – Moskva: Gostekhizdat, 1947. – 539 p. (Rus)

The sanitary-epidemiology requirements for living conditions in living buildings and quarters: SunPiN 2.1.2.2645-10: Approved by Resolution of The state sanitary doctor of the Russian Federation No 64, 10.06.2010: Effective from 15.08.2010. – Moskva, 2010. (Rus)

The calculation of the electric and magnetic fields of the electrical transmission lines: COU-N EE 20.179:2008. – Official edition. – Kyiv: Derzhavne pidpryemstvo "Naukovo-doslidnyi, proektno-vyshukuvalnyi ta konstruktorsko-tekhnologichnyi instytut "Ukrsilenergoproekt": Ministerstvo palyva ta enerhetyku Ukrainy, 2008. – 34 p. (Ukr)

Dezelak K., Stumberger G., Jak F. Arrangements of Overhead Power Line Conductors // Electric Power Systems Research. – 2011. – Vol. 81. – No 12. – Pp. 2164-2170.

Conti R., Giorgi A., Rendina R., Sartore L., Sena E.A. Technical Solutions To Reduce 50 Hz Magnetic

Fields from Power Lines // Proceedings of Power Tech Conference IEEE’2003, 23-26 June, 2003. – Bologna (Italy). – 2003. – Vol .2. – 6 p.

Feychting M., Floderus B. and Ahlbom A. Parental occupational exposure to magnetic fields and childhood cancer // Cancer Causes and Control. – 2000. – Vol. 11. – Pp. 151-156.

Focke F., Schuermann D., Kuster N., Schär P. DNA fragmentation in human fibroblasts under extremely low frequency electromagnetic field exposure // Mutation Research. – 2009. – Vol. 683. – No 1-2. – Pp. 74-83.

The Swedish National standard. MPRII 1990:08. – Swedish Board for Technical Accreditation, 1990.